Recommended Alarms based on device types

Recommended Alarms based on device types

Listed below is a list of sample alarms that can be added for various device types in your facility.

Alert
All the listed alarms are suggestions to our users, users are requested to change the parameter value as per organizational standards/ requirement.

Sl Num

Device Type

 Suggested Alarms

1

Variable Air Volume (VAV)

 Room Temperature greater than 28 C - Threshold

 Room Temperature greater than 28 C for 30 minutes - Threshold with duration

2

Uninterrupted Power Supply (UPS)

 Output voltage greater than 250V - Threshold

 UPS Load greater than 75% - Threshold

 Output Frequency greater than 52Hz - Threshold

3

Energy Meter

 Power factor lesser than 0.8 - Threshold

 Over Voltage - Threshold

 Under Voltage - Threshold

 Load greater than 40kW - Threshold

4

Exhaust Air Fan

 Exhaust Fan in Manual mode - Threshold

 Exhaust fan On in non-specified hours - Threshold

 Exhaust Fan tripped - Threshold

5

Fresh Air Fan

 Fresh Air Fan in Manual mode - Threshold

 Fresh Air Fan On in non-specified hours - threshold

 Fresh Air Fan tripped - Threshold

6

AHU

 AHU in Manual mode - Threshold

 AHU On in non-specified hours - threshold

 AHU tripped - Threshold

 AHU Filter not clean - Threshold

 AHU Fire alarm - Threshold

 AHU Temperature Setpoint lesser than 16 C - Threshold

7

Temperature sensor

 Room Temperature greater than 26 C - Threshold

 Return Air Temperature greater than 30 C - Threshold

8

CO2 sensor

 CO2 value greater than 1000 ppm - Threshold

 CO2 value greater than 800 ppm for 30 mins - Threshold with duration

9

RH sensor

 Ambient humidity greater than 60% RH - threshold

10

Hydrogen sensor

 Hydrogen sensor reading greater than 0.5% - threshold

11

Water Leak Detector

 Water leak detector issue - threshold

12

Auto sequential panel

 Room Temperature is greater than 20 C - threshold

 Temperature setpoint is greater than 20 C - threshold 

13

Breakers

 Breaker is off - threshold

 Breaker tripped - threshold

14
Fire Panel
 Fire Alarm - Threshold



Notes
Not finding any suggestions for your devices OR want help setting up the alarms for your devices
Contact us through support@iqnext.io

    • Related Articles

    • Triggered Alarms Page Overview

      When any device meets the criteria of the alarm rule, an alarm is triggered. When the alarm is triggered selected users will get notified. Users can then check the descriptive details of every alarm trigger through the triggered alarms page. The data ...
    • Handling Alarms once they get triggered

      This document outlines how alarm triggers are defined, how users are notified, and the different states an alarm can go through during its lifecycle on the platform. What is a Alarm Trigger ? An alarm trigger is an event generated when a pre-defined ...
    • Managing Device Alerts

      To check for disconnected devices - IQnext manages a list of the disconnected gateway, wired and wireless devices. You can track the status of disconnected device of a building or a floor here. To access a list of disconnected devices: Log in to your ...
    • Choosing the right dashboard type

      Selecting the right dashboard type is critical for ensuring that each user — whether a Facility Manager, Technician, Supervisor, or Account Manager — has easy access to the insights they need, whether across an entire organization, city, building, or ...
    • Know your Map Icons

      Icons on maps are visual symbols used to represent the device types. They provide quick, intuitive understanding, enabling users to navigate and interpret maps effectively. These icons are standardized by IQnext. Icons transform maps into ...